An inline centrifugal pump carries its suction and discharge nozzles on one horizontal centerline, so the unit sits inside a straight pipe run the way a valve does. Water enters at one flange, a single impeller lifts it, and it leaves at the opposite flange on the same axis. There is no baseplate and no concrete inertia block, because the pipe itself carries the pump. The same shape is sold as vertical inline pumps, since the shaft stands upright with the motor sitting on the casing.

We build the family on one casing, the LD, and ship it in two mounting builds: long-coupled as standard, close-coupled when the plant room is tight. Flows reach 1,200 m³/h and heads run from 1 to 150 m in a single stage. A duty point above that head moves to our vertical multistage range, which stacks impellers on one shaft.

FLOW

To 1,200 m³/h

HEAD, ONE STAGE

1 to 150 m

FLANGE

DN32 to DN300

WATER TEMPERATURE

-10 to +120 °C

FILIPUSI LD series vertical inline pump installed in a horizontal HVAC pipeline, standing on the pipe without a concrete base

An LD pump bolted into a horizontal HVAC header. The piping carries the weight; the plant room floor stays clear.

Inline, End Suction or Multistage

All three spin an impeller inside a volute and push water out. What separates them is where the nozzles point, what has to be built underneath, and how much room the set takes once it is on site. Most projects come down to inline versus end suction, and those two rows decide it.

  Inline, single stage End suction, single stage Vertical multistage
Nozzles Suction and discharge facing each other on one horizontal centerline Suction on the shaft axis, discharge at 90 degrees Suction at the bottom, discharge at the top, vertical centerline
Under the pump Nothing. The pipe carries it Baseplate grouted to a concrete foundation Baseplate on the floor, motor standing above
Floor space Up to 50% less than a horizontal end suction set of the same duty Baseplate plus room to work on the coupling Small footprint, tall, needs ceiling clearance
Head it reaches 1 to 150 m from one impeller Medium head from one impeller To 350 m from stacked impellers, at lower flow
Seal change Long-coupled: back pull-out, motor and piping untouched Coupling and motor come off before the seal Rotating assembly lifted out from the top
Usual duty Chilled and hot water loops, district heating, cooling towers, retrofit work General transfer, boosting, cooling tower supply Building boost, boiler feed, reverse osmosis

When inline is the wrong pick

Three cases go to another pump. A head above 150 m belongs to a multistage unit, because one impeller cannot reach that pressure at a shaft speed the seal and bearings are rated for. Water above 120 °C needs a high-temperature seal on a cooling plan, and the standard cartridge will not hold it. A fluid carrying sand or solids will eat a closed impeller, and an open-impeller end suction pump costs less to keep running.

When multistage has to sit in the pipe

Some jobs need the pressure of several impellers but cannot give up the pipe-mounted layout. We make that too: a tube-type vertical multistage pump that goes straight into the line, with the motor inside a silencing sleeve. Same idea, more head, still no foundation. See inline booster pumps.

One Casing, Two Mounting Builds

Long-coupled, the standard build

A spacer coupling joins motor shaft to pump shaft, and the pump carries its own bearing bracket, so hydraulic thrust never reaches the motor bearings. Motors run from 0.75 to 250 kW, casings are cast iron grade 250 or ductile iron, and the pressure class is PN16 or PN25, with PN40 on request. Take off the spacer coupling and the whole rotating assembly comes out through the back of the casing with the motor still bolted and both flanges unbroken; a seal change usually finishes inside an hour. That is the reason this build is specified for chilled water plants and district heating stations that cannot stop for a day.

Close-coupled, the compact build

The motor bolts straight onto the pump flange. It is shorter, needs less clearance above, and costs less to buy. Same casing, same impeller, same curve, so a duty point can be quoted in either build. The trade is service: the motor has to come off before the seal comes out, which puts a seal change into a planned shutdown rather than an afternoon.

LD inline centrifugal pumps: curves, dimensions and spare parts »

Which Material for Which Water

Wetted parts Where it goes Where it should not
Cast iron 250, ductile iron Clean water, closed HVAC loops, glycol mixes, chilled and hot water headers Seawater, brackish water, chloride-bearing process fluid
SS316L High-purity water, food-side circuits, mild chemical duty, wash-down lines Full seawater duty, where chloride pitting starts at the seal faces first
Bronze Seawater and brackish cooling, shipboard circuits, desalination feed Anything abrasive; pair it with a silicon carbide seal, not carbon
Duplex 2205 High-chloride water, brackish and aggressive process duty, offshore cooling Strong acids or hot concentrated chloride, which need a higher alloy again

Actual photo of the ducted centrifugal pump's ductile iron impeller

Cast iron covers -10 to +120 °C. Past that, the seal changes to a high-temperature cartridge with a cooling plan (Plan 21 or Plan 32) and the pump runs to +160 °C. A pump ordered in duplex or bronze is quoted with a matching shaft and seal, not a standard one.

Setting It Into a Pipe Run

Five points decide whether an inline pump runs quietly for ten years or loses its seal in the first month.

01 Support the pipe on both sides of the pump independently. The casing is not a pipe support, and a flange carrying the weight of a full header will crack at the bolt holes.
02 Keep the motor vertical, with the shaft square to the pipe axis. Leave at least 1.5 times the motor height free above it for lifting gear and seal work.
03 Fit an isolation valve on each side and a drain at the low point, plus a check valve on the discharge so the pump does not run backwards when it stops.
04 Dial-indicate the spacer coupling after the pipe is welded and before the first start, both parallel and angular. Weld heat moves a header more than most fitters expect.
05 Fill and vent the casing, then check rotation. A dry start takes the mechanical seal out in seconds, and that is the most common failure we see on site.

What We Need to Quote a Duty Point

01 Flow, maximum and minimum. The pump should sit near its best efficiency point at design flow; running below half of it recirculates water inside the casing and takes the seal out early.
02 Total head. Static lift, plus friction in pipe and fittings at design flow, plus the pressure the last terminal needs. Above 150 m we quote a multistage unit instead.
03 Fluid and material. Clean water, glycol mix, seawater or process fluid, with the working temperature and the chloride level. That choice is the table above.
04 Electrical. Voltage, frequency, efficiency class, fixed speed or VFD, cabinet IP rating, and whether an Ex motor is needed. 380V/50Hz is standard; 220V, 415V, 440V, 460V and 60Hz builds are quoted on request.

Send the duty point and get a model with a curve. Flow, head, fluid, temperature and voltage are enough to start. The reply carries a performance curve, a dimensional drawing and a price within 24 hours. Request a quote »

Frequently Asked Questions

Q1: What is an inline pump?

A1: A single-stage centrifugal pump whose suction and discharge nozzles face each other on one horizontal centerline, so the pump is bolted into a straight pipe run between two flanges instead of standing on a baseplate. An end suction pump takes water in along the shaft axis and turns it 90 degrees; an inline pump sends it straight through.

Q2: What are the advantages of an inline pump?

A2: No foundation to pour, no baseplate to grout, and up to 50% less floor space than a horizontal end suction set of the same duty. The two flanges line up with the existing header, which is why inline pumps are the usual answer in retrofit work where a foundation is impossible. The vertical shaft also lets the pipe grow with heat along its own axis instead of bending the casing.

Q3: Inline or multistage for my building?

A3: Follow the head. Up to 150 m in one stage, inline covers the duty at high flow and low cost. Above that, a vertical multistage pump reaches 350 m with stacked impellers but runs at lower flow. If you need multistage pressure and still cannot build a foundation, the tube-type inline booster is the third option.

Q4: Does the pump need a concrete base?

A4: No, provided the pipe on both sides is supported by its own brackets or hangers. The failure we see is a pump used as a pipe support: the flanges then carry the header weight and the seal misaligns within weeks.

Q5: Can it run hot water, seawater or glycol?

A5: Cast iron handles clean water to 120 °C, and a high-temperature cartridge with a cooling plan takes it to 160 °C. Seawater needs bronze wetted parts and a silicon carbide seal. Glycol mixes run without change. High-chloride process water goes to duplex 2205.

Q6: How long does a seal change take?

A6: Under an hour on the long-coupled build. The spacer coupling comes off, the rotating assembly slides out through the back of the casing, and the motor stays where it is with the suction and discharge flanges untouched. On the close-coupled build the motor has to come off first, so that work goes into a shutdown.

Q7: How noisy is it?

A7: Below 75 dB(A) at normal operating points, with vibration under the ISO 10816 limits. Balanced impellers and a rigid coupling keep it there, which is what allows the pump in a hotel or hospital mechanical room rather than a plant yard.

Other Pump Categories

Vertical Multistage Pumps

Stacked impellers, heads to 350 m, flows to 270 m³/h: building boost, boiler feed, reverse osmosis. Stainless steel wetted parts.

View multistage pumps »

End Suction Pumps

Horizontal single-stage pumps, close-coupled or back pull-out, for transfer, cooling towers and general duty.

View end suction pumps »

Marine and Seawater Pumps

Bronze and duplex stainless builds for seawater cooling, ballast transfer and desalination duty.

View marine pumps »


 